PT. Bopana Arga Prima Jaya

sql
Kyoritsu Multi Function Tester MODEL 6011A
Hover to Zoom

12 Feb 2020
Japan
1 Unit
IDR CALL

Spesifikasi

Kyoritsu Multi Function Tester MODEL 6011A

• Complies with IEC 61557
• Designed to IP 54 Rating
• Live circuit and wiring connection check LED's
• Triple ranges insulation tests at 250, 500 and 1000V
• Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range(No RCD Trip)
• Phase angle selection on RCD ranges
• Polarity switch for continuity tests
• Auto-null facility for continuity tests
• Earth probe for loop impedance testing on extraneous metalwork
• Contact Voltage Reading
• Test of a large kind of RCD's: Standard, Selective, AC and A
(DC sensitive breakers)

Continuity Testing
Measuring Ranges20/200/2000Ω (Autoranging)
Open Circuit Voltage>6V
Short Circuit Current>200mA DC
Accuracy±(1.5%rdg+3dgt)
Insulation Testing
Measuring Ranges20/200MΩ (Autoranging)
Test Voltage250V 500V 1000V DC
Output Voltage on Open Circuit250V+40%-0%
500V+30%-0%
1000V+20%-0%
Rated Current> 1mA
Accuracy±(1.5%rdg+3dgt)
Loop Impedance Testing
Rated Voltage230V AC +10%-15% [50Hz]
Voltage Measuring Range100 - 250V AC [50Hz]
Impedance Ranges20/200/2000Ω
Nominal Test Current25A (20Ω range) 15mA (200Ω range) 15mA (2000Ω range)
Accuracy20Ω range ±(3%rdg +4dgt)
200Ω range ±(3%rdg +8dgt)
2000Ω range ±(3%rdg +4dgt)
PSC Testing
Rated Voltage230V AC +10%-15% [50Hz]
PSC Ranges200A (15mA Test Current)
2000A (25A Test Current)
20kA (25A Test Current)
AccuracyPSC accuracy derived from measured loop impedance specification
and measured voltage specification
RCD Testing
Rated Voltage230V AC +10%-15% [50Hz]
Trip Current SettingsRCD × 1/2 : 10,30,100,300,500,1000mA
RCD × 1 : 10,30,100,300,500,1000mA
RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A)
Trip Current DurationRCD × 1/2 × 1: 2000ms
RCD fast: 50ms
AccuracyTrip current +10%-0% of test current at 230V
Trip time ±(1%rdg + 3dgt)
Safety StandardIEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61557
Power sourceLR6 (1.5V) × 8
Dimensions130(L) × 183(W) × 100(D)mm
Weight1100g approx.
Included Accessories*KAPM10
(Molded plug test leads for loop and RCD testing at sockets)
7122B (Test leads)
7132A (External earth probe)
Pouch for Test Leads
9121 (Shoulder Strap)
Battery LR6 (1.5V) × 8
Instruction Manual
Optional Accessories7133B (Distribution board test leads)
Multi Function Tester

Multimeter

Ulasan

/5
Ulasan
5
4
3
2
1

Foto dari Pembeli

Ulasan dari Pembeli

Filter
Semua
Dengan Foto
5
4
3
2
1
Telepon
Minta Penawaran
Produk Siap di Pesan
Rp 0
1
Bendera Indonesia Indonesia  |  Bendera Inggris English
Ingin menghubungi kami?
Klik tombol dibawah
Logo IDT
Chatbot